To catalogue

CALTRAN™ 60-30

CALTRAN™ 60-30 transformer oils have excellent dielectric properties, high thermal stability and good resistance to oxidation. CALTRAN transformer oils fully meet ASTM D3487 specifications for Type I and Type II mineral insulating oil in electrical apparatus.

Product families

Applications

Industrial — Chemical & Industrial Manufacturing
  • Equipment & Parts
Industrial — Power, Water & Utilities
  • Power & Utilities

Product Families

Ready-to-Use Products — Fluids & Lubricants
  • Lubricants & Oils

Other characteristics

Brand
CALTRAN
Features

Chemical Resistant, Electrically Insulating, Excellent Dielectric Properties, Good Thermal Stability, Oxidation Resistant

Product Type
Oil
Application Area
Power Transformers
Markets
Industrial
Technology
Ready-to-Use Products
Base Oil
Naphthenic
Product Features

Excellent physical, chemical, and electrical properties; Good oxidation resistance; Rapid heat transfer properties; Outstanding low temperature properties without the need for pour point depressants; Miscible with all comparable hydrocarbon-based transformer oils; Meets ASTM D3487 Type I and Type II application specifications

Transformer Oils

Calumet Specialty Products Partners has over 25 years of experience producing highly-refined, clean, and stable electrical insulating fluids. Calumet is a long standing participant in the Annual DOBLE Survey on transformer oil.. Developed in-house by Calumet's R&D group, CALTRAN transformer oils have excellent dielectric properties, high thermal stability and good resistance to oxidation. CALTRAN transformer oils fully meet ASTM D3487 specifications for Type I and Type II mineral insulating oil in electrical apparatus.

Ready to Use Product Features
  • Chemical Resistant
  • Electrically Insulating
  • Excellent Dielectric Properties
  • Good Thermal Stability
  • Oxidation Resistant

Technical data

Table 1 of 1

26 rows
CharacteristicValueUnitMethod
ColorL0.5—ASTM D1500
Density (at 15.6°C)0.8749kg/dm3ASTM D4052
Dielectric Breakdown Voltage (at 60 Hz Disk Electrodes)min. 40kVASTM D877
Dielectric Breakdown Voltage (at 60 Hz VDE Electrodes, 0.040-In. (1.02-mm) Gap)min. 30kVASTM D1816
Dielectric Breakdown Voltage (at 60 Hz Vde Electrodes, 0.080-In. (2.03-mm) Gap)min. 60kVASTM D1816
Dielectric Breakdown Voltage Impulse Conditions300—ASTM D3300
Flash Point154°CASTM D92, COC
Gassing Tendency18uL/minASTM D2300
Interfacial Tension51dyne/cmASTM D971
Neutralization Number0.014mg KOH/gASTM D974
Oxidation Inhibitor Content0.28mass %ASTM D2668
Oxidation Stability (164 Hours Acid Number)0.01mg KOH/gASTM D2440